Table 4-2.
Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(continued)
56.
Step 2.
Shut down engine and disconnect battery. Check diode 1CR2 (see
malfunction 99).
operational check.
If diode is good, do step 3.
b.
Step 3.
b.
Test ac contactor K1 (malfunction 95).
Step 4.
a.
b.
AC UNDER VOLTAGE INDICATOR DOES NOT LIGHT WHEN %LOAD METER EXCEEDS MAXIMUM
57.
ALLOWABLE FOR THE CURRENT SELECTOR SWITCH SETTING.
NOTE
Maximum allowable %LOAD is:
CURRENT LIMIT
SELECTOR SWITCH
SETTING
MAXIMUM %LOAD
10KW
46%
20KW
94%
30KW
140%