TM 55-1730-229-12
TO 35C2-3-473-1
TB3-CR4
and
resistor
TB3-R1
to
illuminate the CHGR/Bat FAULT light.
(4) The battery charger serves as a
filter. When the battery is fully
charged, the full load of the charger
is not sufficient to keep the ripple
limits. Therefore, load resistor R4
is connected in parallel with the
charger 20 amp section input to
increase the load and keep the ripple
within limits.
Change 8
4-160.1/(4-160.2 blank)