Table 4-2.
Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(continued)
55.
If switch tests good, do step 4.
b.
Remove battery charger access cover. Lower control panel (paragraph
Step 4.
4-24.a). Disconnect main harness connector P7
from control
panel
connector J7, and disconnect harness connector P11 (32, figure 4-38)
from ac contactor K1. Check for continuity between the following
If no continuity,
Check continuity
replace wire no.
From
To
X37B20
J7-17L
1S9-A1-C
X34B20
1M9(-)
J7-15R
X37A20
P7-17R
P11-E
X34A20
P11-F
P7-15L
1S9-A2-C
1M9(+)
X40A20
a. If no continuity, replace indicated wire and perform
operational check.
b. If all continuity checks good, do step 5.
Test ac contactor K1 (malfunction 95).
Step 5.
b. If contactor tests good, replace AC %LOAD meter 1M9
Test AC PHASE SELECT switch 1S9 (malfunction 79).
Step 6.
operational check.
b. If switch tests good, do step 7.
Step 7.
a. Remove battery charger access cover. Disconnect main harness
connector P7 from control panel connector J7.
4-85