Table 4-2.
Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
11.
(continued)
b.
Remove battery charger access cover. Disconnect main harness
connector P6 from control panel connector J6, and disconnect
harness connector P8 from lower tray connector J8. Check for
If no continuity,
From
To
replace wire no.
J6-N
L2A20
1S6-1
P8-S
P6-N
L2B20
58-S
3VR1-pin
G5G20
J8-T
3VR1-screw
G19A20
Replace open wire. After replacement, reconnect all
connectors, and perform operational check.
Test PANEL LIGHTS switch 1S6 (see malfunction 79).
Step 10.
operational check.
b.
If switch is good, do step 11.
Step 11.
Check wiring between switch 1S6-3 and right panel lamp socket
positive terminal.
Replace defective wiring and perform operational check.
Step 12.
Set MASTER SWITCH to OFF and disconnect battery. Check panel light
bulb.
Replace defective bulb with good bulb, and perform
a.
operational check.
b.
If bulb is good, do step 13.
Step 13.
Check wires (L3D20 and L6A20N) between left and right panel light
sockets.
a.
Replace defective wiring.
4-40