TM 55-1730-229-12
AG 320A0-OMM-000
TO 35C2-3-473-1
TM 1730-12/1
Table 4-2.
Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(continued)
92.
i.
Set MASTER SWITCH off, and disconnect battery. Disconnect
one wire from switch (6), and check for continuity between
switch outer terminals with switch actuated (bypass door
open). If continuity exists between switch outer terminals,
check switch wires E22A20 P5-8R to 1S3-C or E40A20N (1S3-NC
graph 4-44). After replacing switch or wires, perform
operational check.
EMERGENCY STOP SWITCH MALFUNCTION.
93.
If an emergency switch malfunction is suspected, teat the switch and wiring as
follows:
and remove battery charger access cover.
b.
Disconnect main harness connectors P4, P5, and p8 from ECU,
control panel harness, and lower electrical tray harness.
Check for continuity between main harness connector pins as
With EMERG
Normal
Measure
Indication
STOP Switch
From
To
Continuity
P8-L
Not pressed
P5-1L
Open
P8-L
Pressed
P5-1L
Continuity
Not pressed
P5-11R
P4-T
Open
P4-T
Pressed
P5-11R
If all measurements are normal, the emergency atop switch and
main wiring harness are good. If any measurement is not
normal, continue with next step.
continuity between switch terminals as follows: