TM
55-1730-229-12
AG
320A0-OMM-000
TO
35C2-3-473-1
TM
1730-12/1
Table 4-2.
Organizational Troubleshooting (continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
(continued)
99.
b.
points listed below. The meter should read less than 25 ohms
when the meter is connected with positive lead on connector
pin, and should read greater than 10K ohms when meter is
connected with negative lead on connector pin. If not the
diode or wire is defective.
Measure
If reading not as
From
To
specified, replace
Fig. Ref.
J5-6R
1DS11(+)
1CR9 or wire E21A20
J5-19L
1DS18(+)
1CR11 or wire P15B20
J5-20R
1CR10 or wire P16B20
1DS19(+)
1CR4 or wire X21B20
J7-9L
1DS17(+1
J7-10L
1DS16(+)
1CR3 or wire X22B20
J7-1R
1S5-2
FO-1
1CR6 or wire P4OA20
1DS11(+)
J7-22L
1CR5 or wire X46B20
J7-12L
lDS14(+)
1CR1 or wire X24B20
J7-11L
lDS15(+)
1CR2 or wire X23B20
PRESSURE TRANSDUCER MALFUNCTION
100.
If the pressure transducer is suspected of malfunctioning, test the transducer
as follows.
a.
Disconnect battery.
b.
c. Check resistance between transducer terminals. Resistance
should be approximately 73 ohms with no pneumatic output. If
resistance is not approximately 73 ohms, replace transducer.
d.
Connect battery and operate system with pneumatic output
terminals, then shut down system.
e.
If resistance was not approximately 10 ohms with pneumatic
output, replace transducer.